Current Transducer LA 100-TP
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.
IPN = 100 A
Electrical data
IPN
Primary nominal rms current
100
A
IPM
Primary current, measuring range
0 ... ±150
A
R M
Measuring resistance @
TA = 70 °C TA = 85 °C
RM min RM max RM min RM max
with ±12 V
@ ±100 A max
0
50
0
42
Ω
@ ±120 A max
0
22
0
14
Ω
with ±15 V
@ ±100 A max
0
110 20 102
Ω
@ ±150 A max
0
33 20 25
Ω
ISN
Secondary nominal rms current
50
mA
KN
Conversion ratio
1 : 2000
U C
Supply voltage (±5 %)
±12 ... 15
V
IC
Current consumption
10 (@ ±15 V) + IS mA
Accuracy - Dynamic performance data
X
Accuracy @ IPN, TA = 25 °C
@ ±15 V (±5 %)
±0.45
@ ±12 ... 15 V (±5 %)
±0.70
εL
Linearity error
< 0.15
Typ Max
IO
Offset current @ IP = 0, TA = 25 °C
±0.10
IOM
Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 × IPN
±0.15
IOT
Temperature variation of IO
−25 °C ... +85 °C
±0.05 ±0.30
−40 °C ... −25 °C
±0.10 ±0.50
tra
Reaction time
< 500
tr
Step response time 2) to 90 % of IPN
< 1
di/dt di/dt accurately followed
> 200
BW
Frequency bandwidth (−1 dB)
DC ... 200
%
%
%
mA
mA
mA
mA
ns
µs
A/µs
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
RS
Resistance of secondary winding @ TA = 70 °C
@ TA = 85 °C
m Mass
Standards
−40 ... +85
°C
−40 ... +90
°C
120
Ω
128
Ω
24
g
EN 50178: 1997
UL 508: 2010
Features
●● Closed loop (compensated)
current transducer using the Hall
effect
●● Insulating plastic case recognized
according to UL 94-V0.
Advantages
●●
●●
●●
●●
●●
●●
●●
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
●● Current overload capability.
Applications
●● AC variable speed drives and
servo motor drives
●● Static converters for DC motor
drives
●● Battery supplied applications
●● Uninterruptible Power Supplies
(UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
●● Industrial.
Notes: 1) Result of the coercive field of the magnetic circuit
2)
With a di/dt of 100 A/µs.
N° 97.10.34.000.0
14January2016/version 10
Page 1/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com
Current Transducer LA 100-TP
Insulation coordination
U d
ÛW
dCp
dCI
CTI
Rms voltage for AC insulation test, 50 Hz, 1 min
2.5
Impulse withstand voltage 1.2/50 µs
7.5
Min
Creepage distance
8.3
Clearance
8.3
Comparative tracking index (group I)
600
kV
kV
mm
mm
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
●● Over voltage category OV 3
●● Pollution degree PD2
●● Non-uniform field
EN 50178
IEC 61010-1
Rated insulation voltage
Nominal voltage
Basic insulation
1000 V
1000 V
Reinforced insulation
600 V
300 V
dCp, dCI, ÛW
Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
14January2016/version 10
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com
Dimensions LA 100-TP (in mm)
dCl
dCp
Connection
IP
IS RM
UC
UC
dCl
Remarks
Mechanical characteristics
●● General tolerance
●● Fastening & connection of primary
Recommended PCB hole
●● Fastening & connection of secondary
Recommended PCB hole
dCp
±0.2 mm
bus bar
6.4 × 1.6 mm
3.8 mm
3 pins
0.6 × 0.7 mm
⌀ 1.2 mm
●● IS is positive when IP flows
IP in the direction of the arrow.
●● Temperature of the primary conductor should not exceed
IS RM
100 °C.
●● Installation of the transducer must be done unless
otherwise specified on the datasheet, according to LEM
U
Transducer Generic Mounting Rules. Please refer to
C
LEM document N°ANE120504 available on our WebUsite:
C
Products/Product Documentation.
●● This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Page 3/3
14January2016/version 10
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com